The minimum span when the commonly used rectangular busbars are arranged relative to the thickness direction of the busbars

Sources :wenhui  Date:2020-07-24 10:58

The minimum span when the commonly used rectangular busbars are arranged relative to the thickness direction of the busbars

 

  For example: for a 31.5kA system, ich takes 80kA, such as for KYN28-12 switchgear a=27.5cm, for TMY100×10 and LMY100×10

Then: L copper MAX≤755 (mm).

L aluminum MAX≤530 (mm).

busbar bending formula

80×10 theoretical value 1680 1830 1900 2160 2475 1340 1460 1530 1725 1980

Recommended value 1400 1400 1600 1800 1800 1200 1200 1200 1400 1400

TMY

80×8 theoretical value 1500 1630 1710 1930 2210 1195 1300 1370 1540 1770

Recommended value 1200 1200 1400 1400 1800 1000 1000 1000 1200 1400

TMY

60×6 theoretical value 970 1060 1110 1255 1440

Recommended value 800 800 800 1000 1000

LMY

100×10 theoretical value 1475 1610 1690 1900 2185 1180 1290 1350 1525 1750

Recommended value 1200 1200 1200 1400 1600 1000 1000 1000 1200 1400

LMY

80×10 theoretical value 1180 1290 1350 1525 1750 945 1030 1080 1215 1395

Recommended value 1000 1000 1000 1200 1400 800 800 800 1000 1000

LMY

80×8 theoretical value 1050 1150 1205 1360 1560 845 925 970 1100 1250

Recommended value 800 800 1000 1000 1200 800 800 800 800 1000

    (Table 2)

The minimum span (mm) when commonly used rectangular bus bars are arranged relative to each other in the width direction of the bus bar:

<img alt="busbar machine turkey" border=0" title="busbar machine turkey" data-original-height="2160" data-original-width="4096" src="https://1.bp.blogspot.com/-Qbr6mhHWWe4/Xv2pCAQJiBI/AAAAAAAAAK0/Chfn0up0EMIcCgOeAB0sYpSnwI-ajUmUwCK4BGAsYHg/w781-h413/busbar%2Bbending%2Bcalculation.jpg" width="781" />

Short-circuit capacity KA/4S 31.5 40

Distance (mm) 275 400 460 275 400 460

TMY

100×10 theoretical value 755 910 980 605 730 780

Recommended value 600 800 800 600 600 600